| Carbon Dioxide Accuracy |
± 40 PPM + 3% rdg |
| Carbon Dioxide Concentration, Max |
2000 ppm |
| Carbon Dioxide Concentration, Min |
0 ppm |
| Carbon Dioxide Response Time |
120 s (τ90) |
| Display Type |
N/A |
| Electrical Output |
4 to 20 mA |
| GrossWeightValue |
0.3 |
| Measurement Type |
Carbon Dioxide, Temperature |
| Mounting Orientation |
North American Style Wall Mount |
| Operating Temperature, Max |
122 °F |
| Operating Temperature, Min |
32 °F |
| Output Detail |
CO2 Output: 4-20 mA / 0 to (5 or 10) VDC |
| Output Signal |
Current, Voltage |
| Power Consumption |
Average: 2 W; Peak: 3.75 W |
| Relative Humidity |
0 to 85% RH Non-Condensing |
| Sensor Life |
15 Years |
| Sensor Type |
NDIR |
| Series ID |
Series-CDT |
| Supply Power Type |
AC/DC |
| Supply Voltage |
19 to 28 Vac/16 to 35 Vdc |
| Switch Type |
N/A |
| Temperature Accuracy |
± 1 °C |
| Temperature Input Range |
32 to 122°F |
| Temperature Output Range |
None |
| Voltage Output Range |
0 to 5 Vdc, 0 to 10 Vdc |
| Country of Origin |
United States |